Call us on 01924 364794  | sales@bpcfixings.com  | technical@bpcfixings.com

VEW2 Windposts

Designed to sit in the cavity itself and tied to both inner and outer leaves, VEW2 Windposts are ideal for more lightly loaded walls.

Introduction

The GA VEW2 range of windposts are of channel section where the post sits in the cavity of the wall, they are generally used for lighter load conditions than the GA VEW1 type posts. 

The use of a GA VEW2 Windpost is governed by the size of the cavity and the load to be supported i.e. it may not be possible to increase the section of the post and therefore its load capacity due to the size of the cavity.

In the case of cast stone units the fixing options are increased as cast-in fixings may also be considered.

Minimum Channel Sections

T (mm)“A”“B”
43520
53525
64035
85550
109080
129080

GA WPTC

The GA WPTC one way tie is clipped to VEW2 edges to tie into both block and brick courses. 

VEW2 WINDPOST CONNECTION EXAMPLES

Example 1

Head fixed using M12 FBN II Anchor into concrete slab.

Base fixed using M12 FBN II Anchor into concrete slab.

Example 2

Head fixed using M12 BSB Bolt into R.H.S.

Base fixed using M12 Isolated Setscrews into steelwork.

Example 3

Head fixed using M12 Coachscrew into timber wallplate.

Base fixed using M12 FBN II Anchor into concrete slab.

Performance Tables

Windposts are designed as simply supported beams with a maximum design strength of 230N/mm2 and a maximum deflection of span/360. Design resistances should be compared with factored loads. Recommended loads include a variance factor of 1.5

VEW2 Windposts – Recommended resistance

Windpost Section SizeRecommended resistance (UDL) kN per post
2.5m3m3.5m4m4.5m5m5.5m6m
65 x 60 x 43.252.31.741.35    
65 x 60 x 53.952.82.11.6    
75 x 60 x 44.33.152.351.85    
75 x 60 x 55.43.862.92.251.75   
85 x 60 x 45.454.053.12.41.95   
85 x 60 x 56.955.093.82.952.351.9  
95 x 60 x 58.66.354.853.83.052.452.05 
105 x 60 x 510.37.7564.753.83.12.552.15
105 x 60 x 611.19.0575.54.43.632.5
115 x 60 x 811.113.310.68.56.855.64.653.9

Bold figures indicate resistance limited by tie capacity / ties required at reduced vertical centres.

VEW2 Windposts – Design resistance

Windpost Section SizeDesign resistance (UDL) kN per post
2.5m3m3.5m4m4.5m5m5.5m6m
65 x 60 x 44.883.452.612.03    
65 x 60 x 55.934.23.152.4    
75 x 60 x 46.454.733.532.78    
75 x 60 x 58.15.794.353.382.63   
85 x 60 x 48.186.084.653.62.93   
85 x 60 x 510.437.645.74.433.532.85  
95 x 60 x 512.99.537.285.74.583.683.08 
105 x 60 x 515.4511.6397.135.74.653.833.23
105 x 60 x 616.6513.5810.58.256.65.44.53.75
115 x 60 x 816.6519.9515.912.7510.288.46.985.85

Bold figures indicate resistance limited by tie capacity / ties required at reduced vertical centres.